Functional Descriptions (By Parameter No.) |
BIAS/GAIN FUNCTION SELECT, BIAS FREQUENCY, GAIN FREQUENCY (Parameter Nos. 56, 57 & 58) |
The relation with the output frequency and frequency setting signal (potentiometer, 0 to 5V, 0 to 10V, 4 to 20mA), can be changed randomly. Use this function according to the application.
(Parameter No. 56 : BIAS/GAIN FUNCTION SELECT)
Data setting range (Hz) | Function details |
0 | Bias/gain function disabled |
1 | Bias/gain function enabled |
(Parameter No. 57 : BIAS FREQUENCY setting)
Data setting range (Hz) | - 99.9 to 400 (0.1 units) |
(Parameter No. 58 : GAIN FREQUENCY setting)
Data setting range (Hz) | 0000 and 0.2 to 400 (0.01 units) (When "0000" is set, OV stop will function.) |
Notes)
1. A frequency exceeding the maximum output frequency or upper frequency clamp cannot be output. The frequency will not drop below the lower frequency clamp.
2. Even if a minus frequency setting signal is input, the inverter will not run in reverse.